Skip to content

120W Industrial Power Supply

  • Industrial control system
  • Factory automation
  • Electro-mechanical apparatus
View Less
View more

Specification

  • OUTPUT
  • DC VOLTAGE48V
  • RATED CURRENT(forBETypeonly) 2.5A
  • RATED POWER120W
  • RIPPLE & NOISE (max.) Note.3< 200 mVpp @ 0°C to +70°C < 600 mVpp @ -30°C to 0°C
  • VOLTAGE ADJ. RANGE43.2 ~ 52.8V
  • VOLTAGE TOLERANCE Note.4 48 Vdc ± 1.0%
  • LINE REGULATION±0.5%
  • LOAD REGULATION±1%
  • SETUP, RISE TIME Note.630 ms typ. @ 115 Vac & 230 Vac
  • HOLD UP TIME (Typ.)10 ms typ. @ 115 Vac (100% load) 16 ms typ. @ 230 Vac (100% load)
  • RATEDCURRENT 2.5A
  • INPUT
  • VOLTAGE RANGE Note.590 ~ 264VAC
  • FREQUENCY RANGE47 ~ 63Hz
  • EFFICIENCY (Typ.)89.5% typ. @ 230 Vac
  • AC CURRENT2.1 A typ. @ 115 Vac, 1.3 A typ. @ 230 Vac
  • INRUSH CURRENT (Typ.) 35A typ./230VAC
  • LEAKAGE CURRENT<0.5mA / 240VAC
  • PROTECTION
  • OVER VOLTAGE< 64.8 V Protection type : Latch Mode, Shut down o/p voltage, re-power on to recover
  • OVER TEMPERATUREProtection type : Latch Mode, Shut down o/p voltage, re-power on to recover
  • ENVIRONMENT
  • WORKING TEMP.-40 ~ +70℃ (Refer to "Derating Curve")
  • WORKING HUMIDITY20 ~ 95% RH non-condensing
  • STORAGE TEMP., HUMIDITY-40 ~ +85℃
  • VIBRATIONNon-Operating: IEC 60068-2-6, Random: 5 Hz to 500 Hz (2.09 G); 20 min per axis for all X, Y, Z direction Operating: IEC 60068-2-6, Sine Wave: 10 Hz to 500 Hz @ 19.6 m/s² (2 G peak); 10 min per cycle, 60 min for X direction
  • SAFETY& EMC
  • SAFETY STANDARDSCB scheme : IEC 62368-1, IEC 61010-1 & -2-201 TUV Bauart : EN 62368-1, EN 61010-1 & -2-201 UL/cUL : UL 62368-1, UL 61010-1 & -2-201 BIS : IS 13252-1 (Part 1) BSMI : CNS14336-1 CCC: GB4943.1 EAC : TP TC 004/2011 KC : K 60950-1 (24 V model only)
  • WITHSTAND VOLTAGEI/P-O/P:3KVAC I/P-Ground :2KVAC O/P- Ground:1.0KVAC
  • ISOLATION RESISTANCEI/P-O/P, I/P-PE, O/P-FG:>100M Ohms / 500VDC / 25℃
  • EMC EMISSIONCompliance to BS EN/EN550 2 (CISPR 2),BS EN/EN61204-3 Class B,BS EN/ 3 3 EN61000-3-2,-3,EAC TP TC 020,CNS13438 Class B
  • EMC IMMUNITYCompliance to EN61000-4-2,3,4,5,6,8,11, EN/BS EN 55035, KN 35 (24 V model only), EN/BS EN 61000-6-2 Compliance to EN/BS EN 61000-6-1 , EN/BS EN 61204-3 IEC/EN/BS EN 61000-3-2, Class A IEC/EN/BS EN 61000-3-3 Voltage Sag Immunity SEMI F47 – 0706 Compliance to FCC Title 47, EN/BS EN 61000-6-3: Class B heavy industry level, EAC TP TC 020
  • OTHERS
  • MTBFTelcordia SR-332 > 700,000 hrs I/P: 115 Vac & 230 Vac, O/P: 100% load, Ta: 25°C
  • PACKING 0.45 kg (0.99 lb)
  • Physical appearance/structure
  • Dimensions30* 123.6 * 116.8 mm (W*H*D)

Specification

Specification
OUTPUT
  • OUTPUT
  • OUTPUT
  • OUTPUT
  • OUTPUT
  • OUTPUT
  • OUTPUT
  • OUTPUT
  • OUTPUT
  • OUTPUT
  • OUTPUT
  • OUTPUT
INPUT
  • INPUT
  • INPUT
  • INPUT
  • INPUT
  • INPUT
  • INPUT
PROTECTION
  • PROTECTION
  • PROTECTION
ENVIRONMENT
  • ENVIRONMENT
  • ENVIRONMENT
  • ENVIRONMENT
  • ENVIRONMENT
SAFETY& EMC
  • SAFETY& EMC
  • SAFETY& EMC
  • SAFETY& EMC
  • SAFETY& EMC
  • SAFETY& EMC
OTHERS
  • OTHERS
  • OTHERS
Physical appearance/structure
  • Physical appearance/structure

Resources

Technical documents

Hikvision.com uses strictly necessary cookies and related technologies to enable the website to function. With your consent, we would also like to use cookies to observe and analyse traffic levels and other metrics / show you targeted advertising / show you advertising on the basis of your location / tailor our website's content. For more information on cookie practices please refer to our cookie policy.

 

Contact Us
Hik-Partner Pro close
Hik-Partner Pro
Security Business Assistant. At Your Fingertips. Learn more
Hik-Partner Pro
Scan and download the app
Hik-Partner Pro
Hik-Partner Pro

Get a better browsing experience

You are using a web browser we don’t support. Please try one of the following options to have a better experience of our web content.