Alarm IO Hub

  • Alarm IO Hub
  • Network
  • POE

Specification
  • Digital Input
  • Number of channels6 single-ended digital inputs (dry contact or common-cathode wet contact)
  • Digital input voltageDry contact Logic level 0: grounding Logic level 1: open circuit Wet contact Logic level 0: 0 to +3 V (maximum) Logic level 1: +10 V to +30 V
  • Working modeDigital input, low-to-high latch, high-to-low latch, counter, and frequency measurement
  • Counter32-bit
  • Counter/frequency input range0 to 3 kHz
  • OtherSupports inverted DI function
  • Digital Output
  • Number of channels6 form-A power relay outputs
  • Contact capacity (resistive)AC: 250 V @ 5 A DC: 30 V @ 3 A
  • Working modeDigital output, low-to-high delay output, high-to-low delay output, and frequency output
  • Breakdown voltage500 VAC (50/60 Hz)
  • Relay switching-on time7 ms
  • Relay switching-off time3 ms
  • Total operating tim10 ms
  • Insulation resistance> 1 GΩ @ 500 VDC
  • Maximum operating frequency20 cycles/min (at rated load)
  • Electrical endurance valueTypical value @30 VDC/3 A: 1 × 105 times (operating frequency: 20 cycles/min) Typical value @250 VAC/3 A: 1 × 105 times (operating frequency: 20 cycles/min)
  • Mechanical endurance valueTypical value: 2 × 107 times (no load, operating frequency: 180 cycles/min)
  • Pulse output frequency≤ 3 Hz
  • Other
  • Isolation voltage2000 V
  • Communication interface10/100 Mbps Ethernet
  • Watchdog timerDouble watchdog timers
  • Power supply voltage+10 V to 30 VDC
  • Power protectionPower reversal protection
  • Power consumption2.5 W @ 24 VDC
  • Operating temperature-10°C to +70°C
  • Storage temperature-20°C to +80°C
Specification
Download Center

This website uses necessary cookies to enable the website to function well. We would like to use additional cookies to provide you the best experience on our website. For more information, please see our cookie policy.